- Clean the chamber from inside and outside after use.
- Check the incoming electric supply of 230 V AC with Neutral and proper earthing.
- The environment should be with proper exhaust fan or air conditioner.
- Clean the condenser by blowing air through it after every 2 months.
- Check whether the air-circulating blower in the AHU is tightened.
- Check the operation of the safety thermostat with reference from OQ.
- Connect proper earthling to the Walk in Type Stability Chamber
- Connect drainpipe connection.
- Close the chamber door properly.
- Check whether the side port hole is properly fitted with rubber cock.
- Calibration and Validation of the Walk in Type Stability Chamber should be done once in a year before the expiry of the due date mentioned.
No. |
REASON |
CORRECTIVE
ACTIONS |
2.1 HEATING EFFECT NOT
ACHIEVED. |
||
2.1.1 |
MCB
may have trip. |
Check the MCB (501&502) If found trip, switch ON it. |
2.1.2 |
DC
output not available. |
Check the 24 VDC output from the SMPS (850&851). Check
the MCB. If found trip, switch ON it. |
2.1.3 |
SSR
not working. |
The DC supply goes from the CPU (951) to the input of
SSR. The SSR is provided with phase connection (502&504) goes to the Air
Heater. If the CPU (951) is giving 24 Volts DC to the SSR input and then checks
which SSR output terminal (504) is not showing the phase (230 Volts) it means
that SSR is not working, this has to be replaced. |
2.1.4
|
Air
heater not working.
|
The phase from the output of the SSR (504) is given to
the heater and the neutral (400) is directly connected. In case the phase and
neutral is provided and still heater is not heating up, it means, that heater
is broken. Also check the heater continuity with the body. If not proper,
then replace the heater. |
2.1.5 |
Safety
Thermostat is not Working. |
Check the safety thermostat and if found not working
replace it. |
2.1.6 |
Chamber
motor not working. |
Check the Motor winding, if found burned out or found
any problem replace it. Check the starting capacitor, If found faulty, replace
it. Check the MCB (601&612) If found trip, switch ON it. |
2.2 HUMIDITY EFFECT
NOT ACHIEVED WITH REGULAR SYSTEM. |
||
2.2.1 |
MCB
may have trip. |
Check the MCB (550&551) if found trip, switch ON it. |
2.2.2 |
DC
output not available. |
Check the 24 VDC output from the SMPS (850&851) Check the MCB. If found trip, switch ON it. |
2.2.3 |
SSR
not working. |
The DC supply goes from the CPU (952) to the input of
SSR. The output of the SSR is provided with a phase connection coming from
the relay RL5 (552) and the other output (554) goes to the Heater. If the CPU
(952) is giving 24 Volts DC to the SSR input and the SSR output terminal is
not showing the phase (230 Volts) it means that SSR is not working, it has to
be replaced. |
2.2.4 |
Relay
not working. |
The DC supply goes from the CPU (954) to the input of Relay
(RL5). The common point of the Relay is provided with a phase connection
(551) and the output (552/NO) goes to the SSR. If the CPU (954) is giving 24
Volts DC to the Relay input and also present the supply (551).But the Relay
(NO/552) output terminal is not showing the phase (230 Volts) that means the
Relay is not working, this has to be replaced. |
2.2.5 |
Heating
element not working.
|
The phase from the output of the SSR (554) is given to
the heater and the neutral (400) is directly connected. In case the phase and
neutral is provided and still heater is not heating up, that means, heater is
broken. Also check the heater continuity with the body. If not proper, then
replace the heater. |
2.2.6 |
12
Volt DC output is not available to the RH sensor. |
12 Volt DC to the sensor is supplied from a 12 VDC power
supply if 12 V is not available at the output of the 12 VDC power supply
replace it. |
2.2.7
|
RH
sensor is not working |
RH sensor output should be between 0 to 1 VDC. Checking
of RH sensor output should be done on Green and Black wire. If the output of
RH sensor is not obtained replace it. |
2.3 HUMIDITY EFFECT
NOT ACHIEVED WITH STAND BY SYSTEM |
||
2.3.1 |
MCB
may have trip. |
Check the MCB (550&571) if found trip, switch ON it. |
2.3.2 |
DC
output not available. |
Check the 24 VDC output from the SMPS (850&851) Check the MCB. If found trip, switch ON it. |
2.3.3 |
SSR
not working. |
The DC supply goes from the CPU (952) to the input of
SSR. The output of the SSR is provided with a phase connection coming from
the relay RL 6 (572) and the other output (573) goes to the Heater. If the
CPU (952) is giving 24 Volts DC to the SSR input and the SSR output terminal
is not showing the phase (230 Volts) it means that SSR is not working, it has
to be replaced. |
2.3.4 |
Relay
not working. |
The DC supply goes from the CPU (955) to the input of
Relay (RL6). The common point of the Relay is provided with a phase
connection (571) and the output (572/NO) goes to the SSR. If the CPU (955) is
giving 24 Volts DC to the Relay input and also present the supply (571).But
the Relay (NO/572) output terminal is not showing the phase (230 Volts) that
means the Relay is not working, this has to be replaced. |
2.3.5 |
Heating
element not working.
|
The phase from the output of the SSR (573) is given to
the heater and the neutral (400) is directly connected. In case the phase and
neutral is provided and still heater is not heating up, that means, heater is
broken. Also check the heater continuity with the body. If not proper, then
replace the heater. |
2.3.6 |
12
Volt DC output is not available to the RH sensor. |
12 Volt DC to the sensor is supplied from a 12 VDC power
supply if 12 V is not available at the output of the 12 VDC power supply
replace it. |
2.3.7
|
RH
sensor is not working |
RH sensor output should be between 0 to 1 VDC. Checking
of RH sensor output should be done on Green and Black wire. If the output of
RH sensor is not obtained replace it. |
2.4 COOLING EFFECT NOT
ACHIEVED WITH REGULAR REFRIGERATION SYSTEM |
||
2.4.1 |
MCB
may have trip. |
Check the MCB (601&604), if found trip, switch ON
it. |
2.4.2 |
Relay
not working. |
The DC supply goes from the CPU (956) to the input of
Relay (RL7). The common point of the Relay is provided with a phase
connection (604) and the output (605/NO) goes to the SSR1. If the CPU (956)
is giving 24 Volts DC to the Relay input and also presents the supply (604).
But the Relay (605/NO) output terminal is not showing the phase (230 Volts)
that means the Relay is not working, this has to be replaced. |
2.4.3
|
Overload
or the capacitor of the compressor not working. |
Check compressor of regular cooling system for overload
and starting and running capacitor for the supply to the compressor. If found
faulty, replace it. |
2.4.4 |
Condenser
Motor not working |
Check the Motor winding, if found burned out or found
any other problem replace it. Check the starting capacitor, If found faulty, replace
it |
2.4.5 |
DC
output not available. |
Check the DC output from the temperature controller
terminals 13 (344) and 14 (345). (Hydronic system) |
2.4.6 |
SSR
not working. (Hydronic system) |
The DC supply comes from the temperature controller
terminal 13 (344) and 14 (345) to SSR terminal 3(+) & 4(-). The output of
the SSR is provided with a phase connection (605) coming from the relay RL 7 and
the other output (606) goes to the compressor. If the controller is giving DC
volt to the SSR input and the SSR output terminal is (606) not showing the
phase (230 Volts) that means the SSR is not working, this has to be replaced. |
2.4.7 |
Chilled
water circulation pump not working. (Hydronic system) Note:
- One number water pump is working at a time. |
Check the water pump winding. Check the starting capacitor. Check for any water line chock up or dust accumulate
inside the impeller. |
2.4.8 |
Unavailability
of chilled water. |
Check the water level inside the Chiller tank. Check for any water leakage from the pipe connection. |
2.5 COOLING EFFECT NOT
ACHIEVED WITH STAND BY REFRIGERATION SYSTEM |
||
2.5.1 |
MCB
may have trip. |
Check the MCB (601&623), if found trip, switch ON
it. |
2.5.2 |
Relay
not working. |
The DC supply goes from the CPU (957) to the input of
Relay (RL8). The common point of the Relay is provided with a phase
connection (623) and the output (624/NO) goes to the SSR2. If the CPU (957)
is giving 24 Volts DC to the Relay input and also presents the supply (623).
But the Relay (624/NO) output terminal is not showing the phase (230 Volts)
that means the Relay is not working, this has to be replaced. |
2.5.3
|
Overload
or the capacitor of the compressor not working. |
Check the compressor of stand by cooling system for
overload and starting and running capacitor for the supply to the compressor.
If found faulty, replace it. |
2.5.4 |
Condenser
Motor not working |
Check the Motor winding, if found burned out or found
any other problem replace it. Check the starting capacitor, If found faulty, replace
it |
2.5.5 |
DC
output not available. |
Check the DC output from the temperature controller
terminals 13 (344) and 14 (345). (Hydronic system) |
2.5.6 |
SSR
not working. (Hydronic
system) |
The DC supply comes from the temperature controller
terminal 13 (344) and 14 (345) to SSR terminal 3(+) & 4(-). The output of
the SSR is provided with a phase connection (624) coming from the relay RL8
and the other output (625) goes to the compressor. If the controller is
giving DC volt to the SSR input and the SSR output terminal is (625) not
showing the phase (230 Volts) that means the SSR is not working, this has to
be replaced |
2.5.7 |
Chilled
water circulation pump not working. (Hydronic system) Note:
- One number water pump is working at a time. |
Check the water pump winding. Check the starting capacitor. Check for any water line chock up or dust accumulate
inside the impeller. |
2.5.8 |
Unavailability
of chilled water. |
Check the water level inside the Chiller tank. Check for any water leakage from the pipe line
connection. |
2.5.9 |
Controller
not working. (Hydronic
system) |
Check the Pt 100 sensor.(Inside the chiller tank) Check the set point. (as per the set condition) |
2.6 CHAMBER MOTOR NOT
WORKING |
||
2.6.1 |
Chamber
motor not working. |
Check the MCB (601 & 612). If found trip, switch it
ON. |
2.6.2 |
Starting
capacitor not working. |
Check the starting capacitor, If found faulty, replace
it. |
2.6.3 |
Motor
burned out. |
Check the Motor winding, if found burned out or found
any problem replace it. |
2.7 PLC PUMA / PUME NOT WORKING |
||
2.7.1 |
No
24V DC Power supply to PUMA / PUME |
Check the MCB (312 & 313). If found trip, switch ON
it. Check SMPS 24V DC. If found faulty replace it. |
2.7.2 |
PUMA
/ PUME not function properly |
PUMA / PUME program may be corrupt. Reload the program. |
2.8 HMI (HUMAN MACHINE INTERFACE) |
||
2.8.1 |
No
Display
|
Check 24V DC power (850 & 851). If not check the
wire for open, 24V DC output from SMPS. If not replace it. |
2.8.2 |
Communication
Failure |
Communication cable faulty. Replace it. |
2.8.3 |
No
printing |
Printer cable may be faulty or loose, reconnect or
replace it. |
2.8.4 |
Any
of the Sensor values are not showing proper |
Wiring connections may be loose or sensor may be faulty,
reconnect or replace it |
2.9 PLC NOT FUNCTIONING PROPERLY |
||
2.9.1 |
PLC
not functioning as per program |
Check the electrical connection to PLC, if not proper
then make proper connections as per electrical diagram, check whether any
loose connections. |
0 Comments